[hardware test]: S7-1200 CPU 1212C V4.7.3, classic S7 — pass (13/13) #907
Copy link
Copy link
Closed
Labels
hardware-testStructured result from a real PLC acceptance runStructured result from a real PLC acceptance runtest-result: passAll selected applicable real-PLC scenarios passedAll selected applicable real-PLC scenarios passed
Description
Source revision
140ccf0 (master, 2026-09-30)
Overall result
pass
PLC family, model, and order code
S7-1200, CPU 1212C; order code not recorded (the runner reports order_code_status: unavailable:AttributeError)
Firmware and security mode
V4.7.3, PUT/GET enabled, non-optimized fixture DBs (DB1 read-only, DB2 scratch)
Host environment
Python 3.11.2 (CPython), Linux x86_64; pytest-bdd 8.1.0, python-snap7 3.2.0; dependencies from uv sync --extra test
Run time (UTC)
2026-09-30T12:35:31Z (the scratch-write run; a read-only smoke run at 12:34:39Z also passed 5/5)
Sanitized report artifacts
JSON report
{
"ended_at": "2026-09-30T12:35:34.443266+00:00",
"environment": {
"architecture": "x86_64",
"implementation": "CPython",
"os": "Linux",
"os_release": "6.1.0-53-amd64",
"pytest_bdd": "8.1.0",
"python": "3.11.2",
"python_snap7": "3.2.0"
},
"overall_result": "pass",
"plc": {
"cpu_state": "S7CpuStatusRun",
"family": "S7-1200",
"firmware": "V4.7.3",
"model": "CPU 1212C",
"order_code": "",
"order_code_status": "unavailable:AttributeError",
"protocol_path": "classic_s7",
"rack": 0,
"security_mode": "PUT/GET, non-optimized fixture DBs",
"slot": 1,
"tia_configuration": ""
},
"scenarios": [
{
"diagnostic": null,
"duration_seconds": 0.25113688403507695,
"scenario_id": "tests/real_plc/test_acceptance.py::test_establish_and_close_a_session",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"smoke"
]
},
{
"diagnostic": null,
"duration_seconds": 0.4527071010088548,
"scenario_id": "tests/real_plc/test_acceptance.py::test_read_the_canonical_fixture",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"smoke"
]
},
{
"diagnostic": null,
"duration_seconds": 0.3205957099562511,
"scenario_id": "tests/real_plc/test_acceptance.py::test_read_multiple_values_in_one_request",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"smoke"
]
},
{
"diagnostic": null,
"duration_seconds": 0.23170647805090994,
"scenario_id": "tests/real_plc/test_acceptance.py::test_reconnect_after_a_clean_disconnect",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"smoke"
]
},
{
"diagnostic": null,
"duration_seconds": 0.20287593704415485,
"scenario_id": "tests/real_plc/test_acceptance.py::test_repeated_operations_do_not_corrupt_the_session",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"smoke"
]
},
{
"diagnostic": null,
"duration_seconds": 0.1367337359697558,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[INT]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.1456899319891818,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[REAL]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.23675779800396413,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[BYTE]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.18378342100186273,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[WORD]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.13081139494897798,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[DWORD]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.13170612300746143,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[DINT]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.1353469750029035,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[CHAR]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
},
{
"diagnostic": null,
"duration_seconds": 0.13723417703295127,
"scenario_id": "tests/real_plc/test_acceptance.py::test_roundtrip_a_value_and_restore_the_plc[BOOL]",
"status": "passed",
"tags": [
"classic_s7",
"real_plc",
"write"
]
}
],
"schema_version": "1.0",
"source": {
"commit": "140ccf08f7bb602b63d2fa074bdedaa5399d8431",
"dirty": false,
"kind": "git"
},
"started_at": "2026-09-30T12:35:31.589977+00:00",
"tester": "@russwing"
}JUnit XML (the hostname attribute redacted)
<?xml version="1.0" encoding="utf-8"?><testsuites name="pytest tests"><testsuite name="pytest" errors="0" failures="0" skipped="0" tests="13" time="2.849" timestamp="2026-09-30T12:35:31.592957+00:00" hostname="redacted"><testcase classname="tests.real_plc.test_acceptance" name="test_establish_and_close_a_session" time="0.252" /><testcase classname="tests.real_plc.test_acceptance" name="test_read_the_canonical_fixture" time="0.453" /><testcase classname="tests.real_plc.test_acceptance" name="test_read_multiple_values_in_one_request" time="0.321" /><testcase classname="tests.real_plc.test_acceptance" name="test_reconnect_after_a_clean_disconnect" time="0.232" /><testcase classname="tests.real_plc.test_acceptance" name="test_repeated_operations_do_not_corrupt_the_session" time="0.203" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[INT]" time="0.137" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[REAL]" time="0.146" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[BYTE]" time="0.237" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[WORD]" time="0.184" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[DWORD]" time="0.132" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[DINT]" time="0.132" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[CHAR]" time="0.136" /><testcase classname="tests.real_plc.test_acceptance" name="test_roundtrip_a_value_and_restore_the_plc[BOOL]" time="0.138" /></testsuite></testsuites>Skips, failures, and notes
- Smoke (read-only): 5/5. Scratch writes (
--allow-write, DB2 only): 8/8 types (INT, REAL, BYTE, WORD, DWORD, DINT, CHAR, BOOL), each restored and read back.--allow-adminoff. - Upload/download on DB2 (the manual check from Formalize real-PLC acceptance testing with Gherkin scenarios #840): the CPU refused
upload(2)withS7ProtocolError: S7 protocol error (class=0x81, code=0x04): This service is not implemented on the module or a frame error was reported.downloadwas not reached. DB2 was byte-identical afterwards (all 38 bytes compared). - Runner notes: the JUnit XML's
hostnameattribute records the test host (redacted above), and the order-code read fails withAttributeError. - Supersedes the earlier smoke-only run on eb6d9e3.
Safety confirmation
- I reviewed the attachments and they contain no PLC address, credentials, private keys, plant/site identifiers, or proprietary PLC program.
Reactions are currently unavailable
Metadata
Metadata
Assignees
Labels
hardware-testStructured result from a real PLC acceptance runStructured result from a real PLC acceptance runtest-result: passAll selected applicable real-PLC scenarios passedAll selected applicable real-PLC scenarios passed
Activity
gijzelaerr commentedon Sep 30, 2026
Thanks for the run! The
order_code_status: unavailable:AttributeErrorwas a bug in the runner: it read the wrong field ofS7OrderCode. Fixed in #908, so the next run will record the order code.test: keep PLC and host details out of real-PLC artifacts
test: keep PLC and host details out of real-PLC artifacts
test: keep PLC and host details out of real-PLC artifacts (#908)
docs: note S7-1200 refusing block upload with 0x81/0x04 (#911)
gijzelaerr commentedon Oct 3, 2026
The runner fixes from #908 are now on master: the order code is read from the right
S7OrderCodefield, and the JUnit XML no longer containshostnameor the PLC address. If you get the chance to rerun on this CPU, please open it as a new result issue and link this one. I'll keep this one open until then, per the result policy.I also added the
upload(2)refusal (class 0x81, code 0x04) to the docs in #911, under PLC feature availability and in the error reference.gijzelaerr commentedon Oct 13, 2026
Recorded in the new Tested and Verified Hardware section of the PLC support matrix (#947). Thanks for the runs!